When operation stops, the cause must be demonstrable

A protective trip, alarm or stopped machine shows what happened last, but not necessarily why. We place electrical data, event logs and the process sequence on the same timeline to distinguish the trigger from the underlying cause.

Event
What stopped, tripped or alarmed and in which order.
Cause
The technical chain that made the event possible.
Action
A measure directed at the verified cause rather than the visible symptom.

The protective trip is not always the answer

The device that trips correctly may only be reporting a problem elsewhere. Without a shared timeline, a final alarm can easily be mistaken for the root cause.

The investigation must preserve the sequence: what changed first, which protections and controls reacted, and how the process responded.

A plausible explanation is not enough. The conclusion must be supported by logs, measurements and a technically coherent event sequence.
Layer 01

Visible event

The trip, alarm, restart or production stop observed by the organisation.

Layer 02

Technical fault chain

The order in which electrical, control and process conditions changed.

Layer 03

Underlying root cause

The condition that must change to reduce the risk of recurrence.

From the electrical system to the process sequence

The investigation boundary follows the event across systems rather than stopping at the first alarm.

Electrical events

Voltage, current, dips, transients and load changes are placed on the event timeline.

  • Electrical quantities
  • Trigger conditions
  • Pre-event data

Protection and selectivity

Settings, fault levels and the order of operation show whether protection behaved as intended.

  • Protection settings
  • Operating order
  • Selectivity

Automation and control

PLC events, interlocks and control sequences are correlated with electrical data.

  • Event logs
  • Interlocks
  • Control sequence

Motors and drive systems

Starting, loading, converter alarms and thermal conditions are assessed in actual duty.

  • Starting and stopping
  • Drive alarms
  • Mechanical load

Process and load

Production state and process changes show what the equipment was being asked to do.

  • Operating state
  • Production sequence
  • Load transition

Recurring patterns

Several events are compared to distinguish a repeated mechanism from coincidence.

  • Common conditions
  • Time correlation
  • Trend and recurrence

Downtime must be understood in the correct order

Clock differences, incomplete logs and missing pre-event measurements can reverse the apparent order of events. We align the available sources and state where the evidence is strong, uncertain or missing.

This prevents a downstream reaction from being treated as the initial cause.

Before

Operating state, load and gradual changes before the event.

During

Electrical event, protection, control response and process reaction.

After

Alarms, restart sequence, damage and conditions for recurrence.

From event log to verified action

The assignment can begin after an event or before recurrence, by preparing the right logging and measurements.

Investigation and analysis

We preserve evidence, align clocks and build a technically coherent sequence.

  • Collect: Logs, settings, diagrams, measurements and process information.
  • Correlate: Place the sources on a common timeline.
  • Test: Compare competing explanations with the evidence.

Action and verification

The response is proportionate to the verified cause and operational risk.

  • Specify: Protection, control, equipment or operating changes.
  • Implement: CLEPS performs or coordinates agreed work in Sweden.
  • Verify: Confirm function and monitor for recurrence under relevant conditions.

Evidence for reducing the risk of the next stop

The report separates facts, interpretations and remaining uncertainty so that corrective work is directed at the supported fault chain.

Depending on scope, it may include:

  • Time-aligned event sequence
  • Relevant electrical and process data
  • Protection and control assessment
  • Tested root-cause hypotheses
  • Documented uncertainty and missing evidence
  • Prioritised corrective measures
  • Verification and monitoring plan
Symptom → chain → root cause

The visible trip is separated from the mechanism that produced it.

Evidence strength

Observed facts, supported conclusions and open questions are reported separately.

Reliability is built before the next stop

Verification confirms that the agreed function has changed. Where recurrence is infrequent, suitable monitoring remains in place so that the next event is captured with better evidence.

A recurring stop should not remain unexplained

Tell us what stopped, which evidence exists and what has already been tried. CLEPS works in Sweden; scope and availability are confirmed for each assignment.